DC Power Flow

The DC power flow model implements network-constrained power flow using Kirchhoff's laws. It is implemented in transmission_dc.jl and based on the cycle-flow formulation from Horsch et al. (2018).

Overview

The DC power flow approximation linearizes the AC power flow equations under the assumptions that:

  • Voltage magnitudes are close to 1 p.u.
  • Voltage angle differences across lines are small
  • Line resistance is negligible compared to reactance

This yields a linear model where power flows are determined by voltage angle differences and line reactances.

Bus vs. Node

ESFEX distinguishes between buses (electrical abstraction) and nodes (geographic locations):

Concept Description Example
Node Geographic location with coordinates City, substation site
Bus Electrical point in the network HV bus, LV bus at same substation

Each bus has a parent_node and carries a demand_fraction of its parent node's total demand. Multiple buses can map to the same node (e.g., different voltage levels at the same substation).

Graph Structures

Incidence Matrix

The bus-line incidence matrix \(\mathbf{K} \in \mathbb{R}^{N \times L}\) encodes the network topology:

\[ K_{n,l} = \begin{cases} +1 & \text{if line } l \text{ leaves bus } n \\ -1 & \text{if line } l \text{ enters bus } n \\ 0 & \text{otherwise} \end{cases} \tag{DC-K} \]

Built by build_incidence_matrix(). Supports parallel lines between the same bus pair (each is a separate column).

Cycle Matrix

The cycle-line matrix \(\mathbf{C} \in \mathbb{R}^{L \times |\mathcal{C}|}\) encodes the independent cycles found via spanning tree analysis:

\[ C_{l,c} = \begin{cases} +1 & \text{if line } l \text{ is in cycle } c \text{ (forward direction)} \\ -1 & \text{if line } l \text{ is in cycle } c \text{ (reverse direction)} \\ 0 & \text{otherwise} \end{cases} \tag{DC-C} \]

Built by find_cycles() using the Graphs.jl library:

  1. Construct a spanning tree of the network graph
  2. Each non-tree edge creates exactly one independent cycle
  3. For each non-tree edge, find the path through the tree between its endpoints
  4. The cycle = tree path + non-tree edge

Constraints

DC-1: KCL (Kirchhoff's Current Law)

Power balance at each bus \(n\) and time \(t\), with transmission losses on incoming flows:

\[ \underbrace{\sum_{g} P_{g,n,t} + \sum_{b} P^{dis}_{b,n,t} + L_{n,t}}_{\text{injection}} - \underbrace{D_{n,t} \cdot \phi_n + \sum_{b} P^{ch}_{b,n,t} + R^{st}_{n,t} + R^{dyn}_{n,t}}_{\text{withdrawal}} = \sum_{l} K_{n,l} \cdot f^{loss}_{l,t} \tag{DC-1} \]

where the loss-adjusted flow is:

\[ f^{loss}_{l,t} = \begin{cases} f_{l,t} & \text{if } K_{n,l} < 0 \text{ (outgoing)} \\ f_{l,t} \cdot (1 - \lambda_l) & \text{if } K_{n,l} > 0 \text{ (incoming)} \end{cases} \]

Here \(\lambda_l\) is the per-line loss factor (from resistance_pu for transmission lines, losses_fraction for transformers).

Injection Terms

The KCL injection also includes EV V2G power, flexible demand curtailed, and converter flows (AC/DC, frequency converters) when applicable.

Implemented in add_dc_constraints!().

DC-2: KVL (Kirchhoff's Voltage Law)

For each independent cycle \(c\), the sum of voltage drops around the cycle must be zero:

\[ \sum_{l \in \mathcal{C}_c} C_{l,c} \cdot X_l \cdot f_{l,t} = 0 \quad \forall c, t \tag{DC-2} \]

where \(X_l\) is the line reactance. For parallel lines, the effective reactance is reactance_pu / num_circuits.

This constraint ensures that power flows are consistent with the physical network impedances, not just the KCL balance.

DC-3: Line Capacity

Each line has a thermal capacity limit:

\[ -\bar{F}_l \leq f_{l,t} \leq \bar{F}_l \quad \forall l, t \tag{DC-3} \]

where \(\bar{F}_l\) is the total transfer capacity, which may include investment:

\[ \bar{F}_l = F^{base}_l + I^{tr}_{l} \]

Implemented in add_line_capacity_constraints!().

DC-4: Voltage Angle Limits

Voltage angle differences across each line are bounded:

\[ |\theta_{n_1,t} - \theta_{n_2,t}| \leq \theta^{max} \quad \forall (n_1, n_2) \in \mathcal{L}, t \tag{DC-4} \]

where \(\theta^{max}\) is the maximum angle difference (default: 30 degrees = 0.524 rad).

DC-5: Slack Bus Reference

One bus is designated as the slack (reference) bus with angle fixed to zero:

\[ \theta_{n^{ref},t} = 0 \quad \forall t \tag{DC-5} \]

By default, bus 1 is the slack bus.

Converter Constraints

AC/DC Converters

AC/DC converters (VSC or LCC type) allow power transfer between AC and DC networks with directional efficiency:

\[ P^{conv}_{n,t} \leq \bar{P}^{conv}_n + I^{conv}_n \tag{CONV-1} \]
\[ P^{ac}_{n,t} = \begin{cases} P^{conv}_{n,t} \cdot \eta^{rect} & \text{rectifying (AC→DC)} \\ P^{conv}_{n,t} / \eta^{inv} & \text{inverting (DC→AC)} \end{cases} \tag{CONV-2} \]

Frequency Converters

Similar to AC/DC converters but connecting networks of different frequencies (e.g., 50 Hz to 60 Hz):

\[ P^{freq}_{n,t} \leq \bar{P}^{freq}_n + I^{freq}_n \tag{FREQ-1} \]

Implemented in add_converter_constraints!().

Transformer Modeling

Transformers are modeled as additional branches appended to the line set:

  • Reactance: Series reactance from reactance_pu field
  • Capacity: Thermal limit from rated_power_mva
  • Losses: Per-transformer losses_fraction
  • Tap ratio: Not modeled in DC approximation (linear model)

Self-loop transformers (both ends at the same bus) are skipped with a warning.

Transmission Losses

ESFEX supports three transmission loss models, selected via dc_power_flow.loss_model:

Mode Key Description Formulation
Lossless "none" No transmission losses \(P^{loss}_{l,t} = 0\)
Linear (legacy) "linear" Constant loss factor on incoming flows (P^{loss}_{l,t} = \lambda_l \cdot
Piecewise linear "pwl" PWL approximation of quadratic \(I^2R\) losses (default) See below

Physical Model

Real power losses on a transmission line are governed by the quadratic relationship:

\[ P^{loss}_l(f) = g_l \cdot f_l^2 \tag{LOSS-PHYS} \]

where \(g_l\) is the line conductance derived from the series impedance:

\[ g_l = \frac{R_l}{R_l^2 + X_l^2} \]

with \(R_l\) the resistance and \(X_l\) the reactance (both in per-unit). Direct inclusion of the quadratic term would make the problem a QP. Instead, we use a piecewise linear (PWL) approximation that preserves LP compatibility.

PWL Approximation

The quadratic loss curve is approximated by \(N\) linear segments (configured via pwl_loss_segments). The flow range \([0, \bar{F}_l]\) is divided into \(N\) equal segments with breakpoints:

\[ f_k = k \cdot \Delta f, \qquad \Delta f = \frac{\bar{F}_l}{N}, \qquad k = 0, 1, \ldots, N \]

The slope of the \(k\)-th segment (\(k = 1, \ldots, N\)) is derived from the secant of the quadratic between breakpoints \(f_{k-1}\) and \(f_k\):

\[ m_k = g_l \cdot (2k - 1) \cdot \Delta f \tag{LOSS-SLOPE} \]

Since \(m_1 < m_2 < \cdots < m_N\) (monotonically increasing slopes), the PWL approximation forms a convex function. This convexity property is critical: for a cost-minimizing LP, the solver will naturally fill lower-slope segments first, so no binary variables are needed to enforce segment ordering.

Flow Decomposition

Because losses depend on the magnitude of flow (not its direction), each line flow is decomposed into positive and negative components:

\[ f_{l,t} = f^{+}_{l,t} - f^{-}_{l,t}, \qquad f^{+}_{l,t}, f^{-}_{l,t} \geq 0 \tag{LOSS-1} \]

Each direction is further decomposed into \(N\) segment variables:

\[ f^{+}_{l,t} = \sum_{k=1}^{N} \delta^{+}_{l,k,t}, \qquad f^{-}_{l,t} = \sum_{k=1}^{N} \delta^{-}_{l,k,t} \tag{LOSS-2} \]

with segment width bounds:

\[ 0 \leq \delta^{+}_{l,k,t} \leq \Delta f, \qquad 0 \leq \delta^{-}_{l,k,t} \leq \Delta f \tag{LOSS-3} \]

PWL Loss Computation

The total loss on each line is the sum of segment contributions from both directions:

\[ P^{loss}_{l,t} = \sum_{k=1}^{N} m_k \cdot \left( \delta^{+}_{l,k,t} + \delta^{-}_{l,k,t} \right) \tag{LOSS-4} \]

Half-Loss Split KCL

Losses are allocated equally between the two endpoint buses of each line. The KCL equation (DC-1) becomes:

\[ \text{net\_inj}_{n,t} = \sum_{l} \left( K_{n,l} \cdot f_{l,t} - \frac{1}{2} \cdot |K_{n,l}| \cdot P^{loss}_{l,t} \right) \tag{LOSS-5} \]

where \(K_{n,l}\) is the incidence matrix entry and \(|K_{n,l}|\) ensures both endpoint buses absorb half the loss regardless of flow direction. This formulation is symmetric and avoids the need to track flow direction for loss allocation.

Configuration

Parameter Default Description
loss_model "pwl" Loss model selection: "none", "linear", or "pwl"
pwl_loss_segments 3 Number of PWL segments for operational dispatch
pwl_loss_segments_master 2 Number of PWL segments for master problem (fewer for performance)

Increasing the number of segments improves accuracy but adds variables and constraints. Three segments typically capture over 95% of the quadratic loss curve.

Power Balance: Single Bus vs. Multi-Bus

Network Size Model Function
1 bus Simple power balance (PB-1) add_demand_constraints!()
2+ buses DC power flow (DC-1 through DC-5) add_dc_constraints!()

The model automatically selects the appropriate formulation based on network.num_buses.

Inter-System DC Power Flow

When multiple power systems are coupled via inter-system transmission links (defined in MetaNetworkConfig.systems_links), ESFEX implements a bidirectional DC power flow model with piecewise-linear loss approximation. This model treats inter-system links as HVDC-like connections with independent voltage references in each system.

Architecture

Unlike intra-system transmission (which enforces Kirchhoff's Voltage Law across all network cycles), inter-system links:

  • Do not enforce KVL across systems (independent voltage angle references)
  • Inject/withdraw power at boundary nodes via the external_injections parameter
  • Model losses using the same PWL approach as intra-system lines (or linear fallback)
  • Support investment in both directions symmetrically

This is analogous to HVDC interconnectors between asynchronous AC systems.

Variables

For each inter-system link \(l\) connecting system A (node \(n_A\)) to system B (node \(n_B\)):

Variable Bounds Description
\(pf_l\) Unbounded Net power flow (positive = A→B, negative = B→A)
\(fp_l\) \(\geq 0\) Forward flow component (A→B)
\(fn_l\) \(\geq 0\) Reverse flow component (B→A)
\(dp_{l,k}\) \([0, \Delta f]\) Segment \(k\) flow (forward direction)
\(dn_{l,k}\) \([0, \Delta f]\) Segment \(k\) flow (reverse direction)
\(ploss_l\) \(\geq 0\) Total power loss on link \(l\)

Constraints

IS-1: Bidirectional Flow Decomposition

The net flow is decomposed into positive (forward) and negative (reverse) components:

\[ pf_l = fp_l - fn_l \tag{IS-1} \]

IS-2 & IS-3: Capacity Limits

Each link has thermal capacity limits in both directions, including investment:

\[ pf_l \leq \bar{F}_l^{base} + \sum_{y} I_{l,y}^{inter} \tag{IS-2} \]
\[ pf_l \geq -\left(\bar{F}_l^{base} + \sum_{y} I_{l,y}^{inter}\right) \tag{IS-3} \]

where \(I_{l,y}^{inter}\) is the inter-system link investment in year \(y\).

IS-4: PWL Loss Approximation

If the link has both reactance_pu and resistance_pu defined, losses are modeled using the same PWL approach as intra-system lines. The link conductance is:

\[ g_l = \frac{R_l}{R_l^2 + X_l^2} \]

Each direction is decomposed into \(N\) PWL segments (configured via inter_system_loss_segments):

\[ fp_l = \sum_{k=1}^{N} dp_{l,k}, \quad fn_l = \sum_{k=1}^{N} dn_{l,k} \]

with segment slopes:

\[ m_k = g_l \cdot (2k - 1) \cdot \Delta f, \quad \Delta f = \frac{\bar{F}_l}{N} \]

The total loss is:

\[ ploss_l = \sum_{k=1}^{N} m_k \left( dp_{l,k} + dn_{l,k} \right) \tag{IS-4} \]

Linear loss fallback: If resistance_pu or reactance_pu is not provided (or if inter_system_loss_segments = 0), the model falls back to:

\[ ploss_l = \lambda_l \cdot |pf_l| = \lambda_l \cdot (fp_l + fn_l) \]

where \(\lambda_l\) is the loss_factor from the config.

IS-5 & IS-6: KCL Injection with Half-Loss Split

The inter-system link injects/withdraws power at the boundary nodes with losses split equally:

System A (FROM bus):

\[ \text{external\_inj}_{n_A} = +pf_l - 0.5 \cdot ploss_l \tag{IS-5} \]

System B (TO bus):

\[ \text{external\_inj}_{n_B} = -pf_l - 0.5 \cdot ploss_l \tag{IS-6} \]

The negative sign on the TO bus ensures power leaves System A and enters System B (accounting for losses).

Configuration

Inter-system transmission links are configured in MetaNetworkConfig.systems_links:

meta_network:
  systems_links:
    - systems: ["SystemA", "SystemB"]
      connections: [[0, 1]]  # Node pairs
      existing_capacity_MW: [500.0]
      max_investment_MW: [500.0]
      investment_cost_per_MW: [1000000.0]
      loss_factor: [0.02]  # Linear loss if R/X not provided
      reactance_pu: [0.01]  # Series reactance (p.u.)
      resistance_pu: [0.001]  # Series resistance (p.u.)
      distance_km: [100.0]
      cost_per_mw_km: [10000.0]
Parameter Type Default Description
reactance_pu list[float] [0.01] Per-link series reactance (p.u.)
resistance_pu list[float] [0.001] Per-link series resistance (p.u.)

Global setting:

Parameter Type Default Description
inter_system_loss_segments int 2 PWL segments for inter-system links (0 = linear fallback, max 5)

Implementation

  • Master Problem: Inter-system variables/constraints are added in master_problem.jl via _add_inter_system_constraints!()
  • Operational Dispatch: Each system receives external_injections kwarg in add_day_operational_constraints!() with link flows computed by the master problem
  • No KVL: Inter-system links do NOT participate in the cycle matrix \(\mathbf{C}\) — each system has independent voltage angle references

References

This formulation is similar to HVDC modeling in production cost models (e.g., PLEXOS, PowerSimulations.jl), where DC links provide controllable power transfer without enforcing AC voltage angle consistency.


N-1 Security-Constrained DC Power Flow

When N-1 security is enabled (n1_security.enabled: true), the optimizer adds contingency constraints ensuring the system remains feasible after the loss of any single critical element.

Critical Element Identification

Not all elements need to be tested as contingencies. ESFEX identifies critical elements to reduce computational burden:

Transmission lines: A line is critical if its base-case loading exceeds the critical_threshold:

\[ \frac{|f_{l,t}|}{\bar{F}_l} \geq \tau^{crit} \quad \text{for any } t \tag{N1-CRIT} \]

where \(\tau^{crit}\) is the critical_threshold (default: 0.50). Lines loaded below 50% in the base case are unlikely to cause issues when outaged.

Generators: The largest online generator (or the generator with the highest output) is tested. The reserve type determines the required generation reserve:

Reserve Type Reserve Requirement
largest_unit Reserve ≥ output of largest online generator
percentage Reserve ≥ reserve_percentage × total demand
fixed Reserve ≥ fixed MW value

Post-Contingency Constraints

N1-1: Line Outage

For each critical line \(l_c\), the remaining network must serve all demand without any remaining line exceeding the post-contingency loading limit:

\[ |f_{l,t}^{(l_c)}| \leq \bar{F}_l \cdot \rho^{post} \quad \forall l \neq l_c, \forall t \tag{N1-1} \]

where: - \(f_{l,t}^{(l_c)}\) is the flow on line \(l\) after outage of line \(l_c\) - \(\rho^{post}\) is the transmission_reserve_factor (default: 0.70)

The post-contingency flows are computed using Power Transfer Distribution Factors (PTDFs):

\[ f_{l,t}^{(l_c)} = f_{l,t} + \text{PTDF}_{l,l_c} \cdot f_{l_c,t} \]

The PTDF matrix describes how the outaged line's flow redistributes across the remaining network.

N1-2: Generator Outage

The system must maintain sufficient spinning reserve to cover the loss of the largest generator:

\[ \sum_{g \neq g_c} \left(\bar{P}_{g,n} - p_{g,n,t}\right) \cdot u_{g,n,t} \geq P_{g_c,n,t} \quad \forall t \tag{N1-2} \]

This ensures that the headroom on committed generators can compensate for the lost unit.

PTDF Matrix Construction

The PTDF (Power Transfer Distribution Factor) matrix is computed from the network admittance matrix:

\[ \text{PTDF} = \mathbf{B}_f \cdot \mathbf{B}^{-1}_{bus} \]

where: - \(\mathbf{B}_{bus}\) is the bus susceptance matrix (imaginary part of admittance) - \(\mathbf{B}_f\) is the branch-bus susceptance matrix

For the DC approximation, susceptances are simply the inverse of reactances: \(b_l = 1/X_l\).

The PTDF matrix is precomputed once and reused for all contingency evaluations.

LODF-Based Fast Contingency Analysis

Line Outage Distribution Factors (LODFs) enable O(1) per-contingency evaluation without rebuilding the B-matrix:

\[ \text{LODF}_{l,k} = \frac{\text{PTDF}_{l,\text{from}_k} - \text{PTDF}_{l,\text{to}_k}}{1 - (\text{PTDF}_{k,\text{from}_k} - \text{PTDF}_{k,\text{to}_k})} \tag{LODF} \]

Post-contingency flow on line \(l\) when line \(k\) trips:

\[ f_l^{(k)} = f_l + \text{LODF}_{l,k} \cdot f_k \]

Both PTDF and LODF matrices are precomputed once and cached. The Python ContingencyAnalyzer uses LODF for analyze_line_loss_fast(), while the Julia SCOPF directly embeds LODF constraints into the optimization.

Contingency Screening

Not all contingencies require full evaluation. The Performance Index (PI) provides a fast screening metric:

\[ \text{PI}_c = \sum_l \left(\frac{f_{l}^{(c)}}{\bar{F}_l}\right)^2 \tag{PI} \]

Contingencies with PI below a threshold (default 1.0) are unlikely to cause overloads and can be skipped. The screen_contingencies() method returns a ranked list of the most critical contingencies.

Transformer Contingencies

Transformers are modeled as branches with their own impedance and thermal rating. When a transformer trips, the B-matrix is rebuilt without that branch, identical to a line outage. Transformer reactance is computed from the tap ratio and short-circuit impedance.

Battery Contingencies

Batteries actively discharging act as generation sources. When a discharging battery trips, the power deficit is redistributed among remaining generators using the same droop-based or pro-rata redistribution as generator contingencies. Only batteries with net injection > 0 are considered.

N-1-1 (N-k) Analysis

Sequential contingency analysis: after the first element trips and power redistributes, a second contingency is evaluated on the stressed system. The analyze_n1_1() method:

  1. Applies the first contingency → post-contingency state
  2. Rebuilds a modified snapshot reflecting the new operating point
  3. Applies the second contingency on the modified state

The screen_n1_1() method identifies the most critical pairs by first finding N-1 contingencies that stress lines above a threshold (default 80% loading), then testing those stressed lines as second contingencies.

Droop-Based Generation Redistribution

When a generator trips, remaining generators can redistribute power using droop-based participation factors instead of simple pro-rata:

\[ \Delta P_g = \frac{(1/R_g) \cdot P^{rated}_g}{\sum_{g'} (1/R_{g'}) \cdot P^{rated}_{g'}} \cdot P^{lost} \]

where \(R_g\) is the generator's droop coefficient. This matches the primary frequency response assumption from the frequency analysis module, providing consistent results between electrical and frequency N-1 assessments.

Security-Constrained OPF (SCOPF)

When scopf_enabled: true, ESFEX replaces the preventive N-1 approach with an iterative SCOPF that adds constraints only for binding contingencies:

  1. Solve base-case dispatch (no N-1 constraints)
  2. Evaluate all N-1 contingencies using LODF
  3. For each violated contingency, add: \(f_l + \text{LODF}_{l,k} \cdot f_k \leq \bar{F}_l\)
  4. Re-solve until no new violations are found (max iterations configurable)

This is more efficient than the preventive approach because only a fraction of contingency constraints are typically binding.

Corrective N-1 Actions

When corrective_enabled: true, post-contingency battery response is allowed:

  • Base-case flows are limited to full line capacity (not reduced by reserve factor)
  • Post-contingency, batteries can adjust charge/discharge to relieve overloads
  • Generator output is also allowed to change within ramp limits

This produces less conservative results than preventive N-1, reflecting the reality that storage-rich systems can respond to contingencies within the frequency response timeframe.

Integrated N-1 Assessment

The IntegratedN1Analyzer combines three security dimensions into a unified assessment:

Dimension Metric Source
Thermal Line overloads, load shedding ContingencyAnalyzer / ACContingencyAnalyzer
Frequency ROCOF, nadir FrequencyAnalyzer
Voltage Bus voltage violations NativeACBridge / PandapowerBridge

Each contingency receives a composite severity score:

\[ S = \underbrace{\max\_\text{overload}\%}_{\text{thermal}} + \underbrace{\frac{P^{shed}}{P^{demand}} \times 100}_{\text{load shed}} + \underbrace{(\Delta f^{lim} - f^{nadir}) \times 20}_{\text{frequency}} + \underbrace{\sum |V^{viol}| \times 100}_{\text{voltage}} \]

N-1 Results in HDF5

When N-1 security is active, the following data is exported to the HDF5 output file under each year's n1_security/ group:

Dataset Shape Description
gen_reserve_duals [hours] Dual of generation N-1 reserve constraint (USD/MW)
trans_reserve_duals/ Group Duals of SCOPF transmission constraints per line/outage pair
binding_contingencies String array Names of binding contingency constraints
security_cost Scalar attr Incremental cost of N-1 security ($)

Configuration

n1_security:
  enabled: true
  transmission_enabled: true
  transmission_reserve_factor: 0.70
  critical_threshold: 0.50
  generation_enabled: true
  reserve_type: largest_unit      # largest_unit, percentage, fixed
  reserve_percentage: 0.15
  scopf_enabled: false            # Use iterative SCOPF instead of preventive N-1
  scopf_max_iterations: 5         # Max SCOPF iterations
  scopf_violation_tolerance: 0.01 # MW tolerance for violation detection
  corrective_enabled: false       # Allow corrective post-contingency actions

Computational Impact

N-1 constraints can significantly increase problem size:

Metric Without N-1 Preventive N-1 (10 lines) SCOPF (10 lines)
Constraints ~10,000 ~110,000 ~15,000-50,000
Variables ~5,000 ~5,000 (same) ~5,000 (same)
Solve time 5-15× 2-8×

To manage computational cost: - Use SCOPF instead of preventive N-1 (adds only binding constraints) - Increase critical_threshold to test fewer contingencies - Use screen_contingencies() with PI threshold to pre-filter - Apply N-1 only in the master problem (representative days) rather than every operational window

Implemented in add_n1_security_constraints!() and add_scopf_constraints!() in power_system.jl. Post-optimization analysis in contingency.py and n1_assessment.py.


Example: 3-Bus System

A simple 3-bus example illustrates the DC power flow formulation:

    Bus 1 (Slack, Gen=200MW)
     / \
  L1/   \L2
   /     \
Bus 2     Bus 3
(D=100MW) (D=80MW, Gen=50MW)
    \     /
   L3\   /
      \ /

Network data:

Line From To Reactance (pu) Capacity (MW)
L1 1 2 0.10 150
L2 1 3 0.15 100
L3 2 3 0.20 80

Incidence matrix K:

L1 L2 L3
Bus 1 +1 +1 0
Bus 2 -1 0 +1
Bus 3 0 -1 -1

One independent cycle: L1 → L3 → L2 (via spanning tree), giving cycle matrix C = [+1, -1, +1]ᵀ

KVL constraint: 0.10·f₁ - 0.15·f₂ + 0.20·f₃ = 0

KCL at each bus: - Bus 1: 200 - 0 = f₁ + f₂ → f₁ + f₂ = 200 (generation minus demand) - Bus 2: 0 - 100 = -f₁ + f₃ → f₃ - f₁ = -100 - Bus 3: 50 - 80 = -f₂ - f₃ → f₂ + f₃ = 30 (net demand = 30 MW)

Solution: f₁ ≈ 96.7 MW, f₂ ≈ 33.3 MW, f₃ ≈ -3.3 MW (reverse flow on L3)


AC Power Flow Verification

The DC power flow approximation is computationally efficient and well-suited for optimization, but it neglects voltage magnitude variations and reactive power. ESFEX provides an optional post-DC AC power flow verification step that runs a full Newton-Raphson solver on the DC-OPF dispatch solution, validating that the operating point is physically feasible under the full AC power flow equations.

Purpose

The AC verification serves as a validation layer, not a re-optimization:

  1. Voltage profile validation — Verify that bus voltage magnitudes remain within acceptable bounds (typically 0.90–1.10 p.u.) under the dispatch solution determined by the DC-OPF.
  2. Reactive power assessment — Compute reactive power flows and generator reactive power output, which are invisible to the DC approximation.
  3. Accurate loss computation — Calculate true \(I^2R\) + \(I^2X\) losses on each branch, including both active and reactive components.
  4. Thermal limit verification — Check branch MVA flows against thermal ratings using the full apparent power (not just active power as in DC).
  5. Violation detection — Flag voltage violations and line overloads that the DC approximation may miss, providing feedback for the planner.

Dual Implementation

ESFEX offers two AC power flow implementations:

Implementation File Engine Use Case
Native Julia NR transmission_ac.jl Custom Newton-Raphson (polar form) Integrated post-dispatch verification
Pandapower bridge pandapower_bridge.py pandapower Newton-Raphson GUI analysis, IEC 60909 short-circuit

Julia Newton-Raphson (transmission_ac.jl)

The native solver implements the standard Newton-Raphson method in polar coordinates:

  • Y-bus construction from line impedances (π-model) and transformer models (with tap ratio)
  • Bus classification: Slack (reference, known \(|V|\) and \(\theta\)), PV (generators, known \(P\) and \(|V|\)), PQ (loads, known \(P\) and \(Q\))
  • Jacobian: 4-submatrix structure \(\mathbf{J} = [H, N; M, L]\) where \(H = \partial P/\partial\theta\), \(N = \partial P/\partial|V|\), \(M = \partial Q/\partial\theta\), \(L = \partial Q/\partial|V|\)
  • Convergence: \(\max(|\Delta P|, |\Delta Q|) < \epsilon\) (default \(\epsilon = 10^{-6}\))
  • Initialization: DC voltage angles as warm-start for \(\theta\), flat start (1.0 p.u.) for \(|V|\)

The solver takes the DC-OPF dispatch result and network data as input, and returns per-bus voltages, per-branch active/reactive power flows, total losses, voltage violations, and line overloads.

Native AC Power Flow Bridge (native_ac_bridge.py)

The native AC bridge uses the Julia Newton-Raphson solver (transmission_ac.jl) directly from the GUI, without requiring external dependencies. It converts the Studio state (GuiSystemState) into flat arrays, passes them to Julia via solve_gui_ac_power_flow(), and returns results in the same ACPowerFlowResult format used throughout the analysis pipeline.

The bridge implements the same duck-typed interface as the pandapower bridge, making it a drop-in replacement for AC power flow and N-1 contingency analysis. The GUI prefers the native bridge when available and falls back to pandapower automatically.

Pandapower Bridge (pandapower_bridge.py)

The pandapower bridge is now used exclusively for IEC 60909 short-circuit analysis (ikss, ip, sk) via pandapower.shortcircuit.calc_sc(). AC power flow has been migrated to the native Julia solver, reducing the external dependency footprint.

AC Contingency Analysis

The ACContingencyAnalyzer extends N-1 security analysis to the AC domain:

  • For each contingency (generator or line loss), the element is taken out of service in the bridge network
  • For generator loss: output is redistributed pro-rata to remaining dispatchable generators based on headroom
  • AC power flow is re-solved; if it diverges, the analysis falls back to DC contingency results
  • Post-contingency results include voltage magnitudes, reactive power, line loading percentages, and voltage violation detection
  • The analyzer is backend-agnostic: it works with both NativeACBridge (default) and PandapowerBridge through duck typing

Configuration

Parameter Default Description
max_iterations 50 Maximum Newton-Raphson iterations
tolerance 1e-6 Convergence tolerance on power mismatch
base_mva 100.0 System base power for per-unit conversion
voltage_min_pu 0.90 Lower voltage magnitude limit
voltage_max_pu 1.10 Upper voltage magnitude limit

References

The DC power flow approximation is formally analyzed by Stott et al. [1]. The general power systems analysis framework follows Glover et al. [41]. PTDF and LODF factors for fast contingency screening follow Van Hertem et al. [42] and Guler et al. [43]. Security-constrained OPF with post-contingency corrective actions follows Capitanescu et al. [34] and Monticelli et al. [44]. Performance index-based contingency screening follows Ejebe and Wollenberg [45]. AC power flow verification uses Newton-Raphson as implemented in MATPOWER [46] and pandapower [47].

See the full bibliography for complete citation details.